the locations shown by yellow lines on Exhibit "A", dated May 12, •*•954,^.attached hereto and by this reference incorporated herein, the following: a* Approximately 2,500 LF of 8" cast iron water mains* b* Approximately 3,130 LF of 6" cast iron water mains* c. Approximately 42 connections* LF of cast iron fire hydrant The cost of constructing said water mains (exclusive of constructing 42 LF of cast iron fire hydrant connections) is the agreed sum of f18,765*00* 2. Said water mains shall be constructed of 8" and 6" Class 150 B & S cast iron pipe and shall b^ in accordance with Federal Specifications WWP 421 Type 1* All joints shall be cement* All fittings shall be new, all bell cast iron e<|ual to ASA Standard Class 250* All valves shall be double disk, parallel seat bronze mountings conforming to AWWA Standards, not less than 175 lbs*, and all valve boxes shall be of cast iron of appropriate size for each valve* Unless otherwise approved by a duly authorized representative of the Company, all pipe valves and fittings shall be manufactured by the Pacific States Cast Iron Pipe Company or Mueller Company* All pipe lines shall be chlorinated in accordance with AWWA Specifications, shall be subject to the approval and acceptance of -State and City Health Authorities, and shall be constructed at an elevation to be designated by a duly authorized representative of the Company, but in no event shall there be less than 36" of covering over such water mains* All workmanship, material and installation of said water mains shall be subject to the