Information
Details
More Info
Transcription
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 (e) Approximately 150 LF of 6" cast iron fire hydrant connection, in location as shown in yellow on the map hereto attached and by reference made a part hereof* The cost of constructing said water mains (exclusive of cost of constructing the said 150 LF of 6M cast iron fire hydrant connections) is the agreed sum of FIFTY THREE THOUSAND & NO/lOO ($53,000.00) DOLLARS, the expense of which shall be borne by the Owner* 2. Said water mains shall be constructed of 12”, 10", 8" and 6” cast iron pipe and shall be in accordance with AWWA specifications. All joints shall be cement and all pipe shall be new B & S cast iron, equal to AWWA Class 150, All fittings shall be new, all bell cast iron equal to AWWA Class 150, and all valve boxes shall be of cast iron of appropriate size for each valve. Unless otherwise approved by a duly authorized representative of the Company, all pipes, valves and fittings shall be manufactured by Pacific States Cast Iron Pipe Company or Mueller Company. All pipe lines shall be chlorinated in accordance with AWWA specifications, shall be subject to the approval and acceptance of State and City Health Authorities, and shall be constructed at an elevation to be designated by a duly authorized representative of the Company, but in no event shall there be less than 36» of covering over such water mains. All workmanship, material and the installation of said water mains shall be subject to the approval and acceptance by a duly authorized representative of the Company. 3. At Owner’s sole cost and expense to survey and ac- - 2 - X-//5